Customization: | Available |
---|---|
After-sales Service: | 7*24 Online Service |
Principle: | Magnetic Sensors |
Still deciding? Get samples of US$ 3000/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1-4meter Stainless Steel Oil Diesel Density Fuel Tank Level Gauge for Gas Station
What are Tank Level Gauge used for?
Gas station tank level gauge are used for monitoring fuel level, volume and temperature inside fuel storage tanks. It is widely used at gas station and skid-mounted fueling site. It also can be used at chemical factory, pharmacy industry and waste water tanks.
The tank level gauge smart console is a powerful product developed and produced by Windbell. Together with SP300 series magnetostrictive liquid level meter constitute the complete automatic tank level gauge system.
The smart console is the display terminal of the automatic tank level gauge system and can detect 1 to 32 tanks at the same time. It can monitor product level, water level, temperature, product volume, water volume, empty volume, all kinds of alarms, inventory and delivery information in real time.
International graphic touch screen and user-friendly icon, makes it is easy for new user.
SP300D Magnetostrictive fuel density sensor is mainly composed of probe head, temperature sensors, protection steel pipe, magnetostrictive waveguide wire and floaters with magnet inside. Insert probe into underground tank, floaters float on the liquid surface, and slides up and down on rod according to the changes of liquid level. Processing measured data of product level, water level, density values, and average temperature of five-points, then transmit these data to smart console by digital communication port.
Tank Level Gauge Smart Console SS200B | |
Power | AC90~276V, 47~440Hz |
Working temperature | -20 to 60ºC (-4 to 140F) |
Display | 12-inch LCD touch screen, 800x600 resolution |
Ex-proof grade | [EX ia Ga] IIB |
Monitor probes | Standard is 8,Up to 32, |
Leak sensor | Support |
Relay output | 2 groups. Node capacity AC250V/3A. DC30V/3A |
SMS module | Optional |
GPRS module | Optional |
Running/Alarm indicator | Yes |
WIFI function | No |
Inventory and delivery management | Yes |
Density and mass measurement | Yes |
Output voltage | DC 12V |
Safety barrier | WB-GSB06 |
Built-in printer | Optional |
External printer | Support |
RS485 port | 1 |
RS232 port | 2 |
USB port | 1 |
Ethernet port | 1 |
Buzzer alarm | Yes |
External sound-light alarm | Support, optional |
Tank table | Yes, simulate/input/upload |
Reports | Inventory, delivery, shift, alarm, leak detection test, system log, SMS for optional |
PC remote software | PCR200 |
Anti-theft function | Yes |
Dimension (L*W*H) | 42*36*16CM |
Magnetostrictive Fuel Density Sensor SP300D | |
Power supply | DC12V |
Precision | ±0.5mm |
Repeatability | ±0.1mm |
Resolution of product level | 0.0069mm |
Resolution of temperature | 0.0078ºC |
Resolution of water level | 0.0069mm |
Temperature range | -40 to 85ºC(-40 to 185ºF) |
Points of temperature measured | 5 |
Maximum communication distance | 1200m |
Communication | RS485 |
Intrinsic safety parameter | Power port: Ui = 15V DC, Ii= 400mA, Pi = 1.5W, Ci = 3.63μF, Li = 0mH; Signal port: Ui = 7.14V DC, Ii= 147mA, Pi = 260mW, Ci = 32.6μF, Li = 0mH; |
Associated apparatus | WB-GSB03 safety barrier |
Explosion proof grade | Ex ia IIA T4 Ga, II 1G Ex ia IIA T4 Ga |
Protection grade | IP68 |
Applicable medium | Gasoline, diesel |
Definition of wires | Blue - Power +, Brown - RS485A , White - RS485B, Black - Power - |
Communication address | 6 digits, see the"Manufacturing code"or S/N code on probe nameplate, this is also Probe ID in communication with console and FMS |
Density measure range | 690Kg/m³~900Kg/m³, (Gasoline: 0.70~0.78g/cm3; Diesel: 0.80~0.89g/cm3) |
Accuracy of density measurement | 3Kg/m³ |
Resolution of density measurement | 0.1Kg/m³ |